Circulation units
for solar thermal systems, with solar regulator DeltaSol® C+
28199
268-269 series
Function
Circulation units are used on the primary circuit of
solar thermal systems to control the temperature
in the hot water storage. The pump inside the
units is activated by the signal arriving from the
regulator. Moreover, safety and functional devices
for optimum control of the circuit are fitted in the
units.
They are available with flow and return connection
or with return connection only.
Some versions are also complete with the digital
regulator DeltaSol
®
C+ for solar thermal systems,
suitable for the operation and control of 9 different
types of solar thermal systems.
1
INDEX
Function
Product range
Technical specifications
Characteristic components
Installation
Filling the system
Commissioning
1
2
3
4
5
6
Components
7
Application diagrams
8
INSTALLATION AND COMMISSIONING MANUAL
Przeglądanie stron 0
1 2 3 4 5 6 7 8

Podsumowanie treści

Strona 1

Circulation unitsfor solar thermal systems, with solar regulator DeltaSol® C+28199268-269 seriesFunctionCirculation units are used on the primary circ

Strona 2

NOTICEThe following instructions must be read and understood before installing, commissioning andservicing the circulation unit.The safety symbol is u

Strona 3 - 13 l/min

3Technical specificationsMaterialsShut-off valvesBody: brass EN 12165 CW617NCheck valve: brass EN 12164 CW614NTemperature gauge: steel / aluminiumAir

Strona 4 - C+ regulator

4Characteristic components1) Grundfos Solar 15-65 circulation pump2)Safety valve with adjustable outlet type 253 series3) Fill/drain cock with control

Strona 5

5Installation• Fix the wall support bracket, using the fixing screws supplied in the pack (1).• Insert the rear insulation, through the notch provided

Strona 6

Commissioning• Close the flow meter fil/drain cock (1) and increase the system pressure up to the maximum design pressure, by means of the external fi

Strona 7

Shut-off and check valvesThe shut-off valves are equipped with a built-in check valve,positioned inside the ball.1. To allow the passage of

Strona 8 - Automatic

Application diagramsShut-off valvePumpAir ventExpansion vesselTemperature gaugeSafety relief valveAutomaticfilling202040608010012014016002040608010012